Persons using assistive technology might not be able to fully access information in this file. For assistance, please send e-mail to: [email protected]. Type 508 Accommodation and the title of the report in the subject line of e-mail. Outbreak of Legionnaires' Disease Among Automotive Plant Workers --- Ohio, 2001During March 12--15, 2001, four cases of Legionnaires' disease (LD) among workers at an automotive engine manufacturing plant (plant X) were reported to the Cuyahoga County Board of Health, Cleveland, Ohio; all four diagnoses were confirmed by Legionella urine antigen. Illness onset among the four workers occurred during March 2--4; two workers died. Beginning March 14, CDC assisted state and local health departments with an investigation to identify new cases and potential sources of Legionella transmission in the plant. This report summarizes the investigation; findings indicate an epidemiologic association with exposure to one of the plant finishing lines but did not identify a specific source. Plant X manufactures cast iron engine components, is operated by approximately 2500 employees, and covers approximately 1.6 million square feet of floor space. The plant is divided into four areas: core making, mold production, iron melting, and finishing. A confirmed case of LD was defined as radiograph-confirmed pneumonia and laboratory evidence of Legionella infection, defined as a positive Legionella urine antigen or isolation of Legionella from respiratory secretions or lung tissue. Specimens from the four initial case-patients were sent to CDC for isolation of Legionella; available specimens included one sputum specimen, one broncho-alveolar lavage specimen, and lung tissue from the two decedents. Active LD surveillance was established in all hospitals in the greater Cleveland area. Hospital records and plant X employee absentee records were reviewed to identify additional cases. An environmental investigation was conducted to identify aerosol-producing water sources for Legionella transmission, including cooling towers, water hoses, and water heaters. No additional confirmed LD cases were identified among the workers. Nine workers from plant X were hospitalized during February 14--March 28; four had pneumonia, and all nine had negative Legionella urine antigen tests. Legionella pneumophila, serogroup 1, was isolated from a worker's sputum sample, which was stored at 40 F (4 C) for >1 week before culture. Results are pending from lung tissue samples. Legionella was isolated from 18 (9%) of 197 environmental samples, and at least five species were identified. Three samples grew L. pneumophila, serogroup 1; none matched the clinical isolate by monoclonal antibody staining. A case-control study was conducted to determine risk factors for exposure to Legionella among plant workers. A case-patient was defined as a worker at plant X during February 14--March 28 who had either a confirmed case of LD or a possible case of legionellosis. A possible case-patient of legionellosis was defined as a worker with a titer of anti-legionella IgG antibody >1:1024 and any two of the following symptoms: cough, shortness of breath, fever, headache, myalgia, or fatigue. Controls were randomly selected workers with fewer than two symptoms and IgG antibody <1:64. Serologic specimens were collected 4--5 weeks after the presumed exposure. Each study participant was asked detailed questions about time spent inside and outside of the plant and information about underlying medical conditions associated with LD. Among 855 workers who were contacted, 484 (57%) agreed to participate in the case-control study; 11 met case criteria (four confirmed and seven possible cases), and 105 met criteria for controls. Visiting one of the finishing lines in the plant (odds ratio [OR]=15.1; 95% confidence interval [CI]=3.0--76.2) and working in the finishing region of the plant (OR=3.8; CI=1.0--13.8) were associated with disease. Plant X was closed during March 14--19 to facilitate environmental sampling and decontamination. All water systems were decontaminated, and ongoing environmental surveillance for Legionella was implemented throughout the plant, including the finishing area. Sources of aerosolized water from the finishing area that had been sampled before decontamination did not yield cultures positive for Legionella. On the basis of the case-control study results, additional environmental samples were collected in the finishing area on April 14; all samples were negative for Legionella. County health officials are obtaining maintenance records from the implicated area of plant X to determine how transmission might have occurred. Reported by: T Allan, T Horgan, H Scaife, Cuyahoga County Board of Health, Cleveland; E Koch, S Nowicki, MK Parrish, E Salehi, Ohio Dept of Health. Respiratory Diseases Br, Div of Bacterial and Mycotic Diseases, National Center for Infectious Diseases; Hazard Evaluations and Technical Assistance Br, Div of Surveillance, Hazard Evaluations and Field Studies, National Institute for Occupational Safety and Health; and EIS officers, CDC. Editorial Note:Industrial plants can be a source for the propagation and transmission of Legionella. The identification of L. pneumophila in the environmental samples demonstrated that legionellae can survive in this work environment. The tightly clustered onset of illness, lack of other epidemiologic associations among the four confirmed patients besides working in plant X, and the results of the case-control study implicated a particular finishing line within the plant as the likely source of Legionella. The narrow period of illness onset and the failure to identify new cases among plant workers suggest that exposure to the infecting Legionella strain was short-lived and transient, which may explain the failure to find an environmental sample that matched the clinical isolate. LD outbreaks have been reported in industrial settings, including an automotive plant where workers were exposed to contaminated metal-working fluids (1), factories that used water to cool molded plastics (2), and waste-water treatment facilities (3). In each setting, an aerosol-producing device was implicated. Guidelines to minimize the risk for Legionella transmission in these sites are available (4). In addition to LD, clinicians should consider hypersensitivity pneumonitis, metal fume fever, and humidifier fever as possible diagnoses of an acute febrile respiratory illness with systemic symptoms in persons who work in an industrial setting (5). Legionella species are estimated to account for 2%--15% of all community-acquired pneumonia; however, only 1200--1500 cases are reported annually (6,7). Appropriate diagnostic testing for LD includes Legionella urine antigen and culture of respiratory secretions. Legionella urine antigen tests provide rapid and accurate diagnosis of disease caused by L. pneumophila, serogroup 1; however, these tests do not identify less common species or serogroups and do not provide an isolate necessary to compare clinical with environmental isolates during outbreak investigations. LD also can be diagnosed by a four-fold rise in anti-legionella antibody titer or by direct fluorescent antibody on sputum samples, although the latter method lacks specificity and sensitivity. In addition to testing for Legionella urine antigen, the diagnosis and investigation of LD cases would be improved if clinicians obtained respiratory specimens for culture by a laboratory proficient in Legionella isolation. To facilitate appropriate investigation and improve understanding of disease associated with Legionella species, health-care providers should report legionellosis cases to county or state health departments, and state health departments should report legionellosis cases to CDC. References
Disclaimer All MMWR HTML versions of articles are electronic conversions from ASCII text into HTML. This conversion may have resulted in character translation or format errors in the HTML version. Users should not rely on this HTML document, but are referred to the electronic PDF version and/or the original MMWR paper copy for the official text, figures, and tables. An original paper copy of this issue can be obtained from the Superintendent of Documents, U.S. Government Printing Office (GPO), Washington, DC 20402-9371; telephone: (202) 512-1800. Contact GPO for current prices. **Questions or messages regarding errors in formatting should be addressed to [email protected].Page converted: 5/10/2001 |
|||||||||
This page last reviewed 5/10/2001
|