Fatal Case of Legionnaires’ Disease After Home Exposure to Legionella pneumophila Serogroup 3 — Wisconsin, 2018

Amy Schumacher, PhD1,2; Anna Kocharian, MS2; Amanda Koch, MPH2; John Marx, MPH3 (View author affiliations)

View suggested citation

Summary

What is already known about this topic?

Legionnaires’ disease is a severe pneumonia caused by the waterborne bacteria Legionella. The rate of reported cases in the United States increased 4.5-fold from 2000 to 2015.

What is added by this report?

Investigation of a culture-confirmed fatal case of Legionnaires’ disease reported in January 2018 identified the patient’s home as the infection source. Legionella bacteria remained following a remediation attempt.

What are the implications for public health practice?

Increased efforts to understand the burden (i.e., morbidity and mortality) and risk for Legionnaires’ disease associated with residential settings and the usefulness and feasibility of testing and remediation in these settings could inform prevention guidance. Lower respiratory tract specimens have value for both patient treatment and public health investigation.

Article Metrics
Altmetric:
Citations:
Views:

Views equals page views plus PDF downloads

Related Materials

In January 2018, the Wisconsin Department of Health Services, Division of Public Health (DPH), received a report of a culture-confirmed case of Legionnaires’ disease. The patient, who was immunocompromised, had died at a local hospital 10 days after being admitted. DPH and an infection preventionist from the hospital investigated to determine the source of the infection and prevent additional cases. Because the case was suspected to be nosocomial, health care facility water samples were tested for Legionella. When these samples were negative, water sources in the patient’s home were tested. These tested positive for Legionella pneumophila, and the bacteria remained after an attempt to remediate. The patient and home isolates were identified as L. pneumophila serogroup 3, sequence type 93, by whole-genome multilocus sequence typing. A second resident of the home did not become ill. This case highlights the potential for immunocompromised persons and others at risk for Legionnaires’ disease to be exposed to Legionella through home water systems containing the bacteria and demonstrates the difficulty of home remediation. This case also illustrates the role of lower respiratory tract specimens in the identification of less common Legionella infections (e.g., L. pneumophila serogroup 3) and confirmation of the infection source.

Investigation and Results

The case occurred in a Wisconsin resident, a nonsmoker aged 70–79 years who had received a 2016 diagnosis of late-onset combined immunodeficiency of undetermined etiology after developing two opportunistic infections that year. The patient was admitted to a local hospital (day 0) (Figure) after evaluation in the emergency department for a rash and fever suspected to be a reaction to oral antibiotics. The patient had been prescribed a 30-day course of oral antibiotics (levofloxacin) following a course of parenteral antibiotics for management of cellulitis of the lower leg with accompanying abscesses. The rash and fever developed near the end of the course of oral antibiotics, which was stopped a day early. On admission, a family member reported recent mental status changes in the patient, and the patient complained of a dry cough and shortness of breath. A respiratory virus panel on sputum detected rhinovirus and parainfluenza 1, but a chest radiograph was normal.

After admission, the fever continued, and mental status changes worsened. The cough became productive with dark brown sputum on day 5; a chest radiograph showed a new right upper lobe opacity. The patient developed septic shock, thought to be attributable to hospital-acquired pneumonia, and was transferred to the intensive care unit. Intravenous aztreonam and vancomycin were initiated, with aztreonam replaced by meropenem later in the day. On day 6, a urinary antigen test for L. pneumophila serogroup 1 and culture of a bronchoalveolar lavage (BAL) fluid specimen for Legionella were ordered; the urinary antigen test result was negative. Inhaled tobramycin was initiated on day 7. Vancomycin and tobramycin were discontinued on day 8. The patient died on day 10, noted in the medical record as the result of cardiopulmonary arrest secondary to septic shock. On day 16, the Wisconsin State Laboratory of Hygiene (WSLH) isolated L. pneumophila from the BAL fluid culture. The isolate was identified on day 17 as L. pneumophila nonserogroup 1 by direct fluorescent antibody and determined later in the investigation to be serogroup 3, which is not detected by the urinary antigen test. Serogroup 3 is not often reported as a cause of Legionnaires’; serogroup 1 accounts for most infections (1).

The hospital’s water management program requires certain actions to be taken in the event that any patient tests positive for Legionella by culture or urinary antigen test with symptom onset indicating possible nosocomial acquisition (i.e., inpatient for more than 2 days or discharged from an inpatient location within 10 days). The program was instituted as a result of a Legionnaires’ disease outbreak during the 1990s and involves targeted environmental cultures. Whereas targeted sampling is typical, this hospital also had the capacity to culture for Legionella in-house. Nine water sources (inpatient and outpatient sink faucets, ice machines, a shower, and a warm water pool) where the patient might have been exposed were sampled (day 17) (Table). Samples were cultured for Legionella at the hospital; all culture results were negative. Additional samples were collected on day 40 and cultured for Legionella at both the hospital and WSLH for validation. All culture results were negative.

On day 26, and at the request of the patient’s family, staff members from the hospital collected and cultured samples from two showers in the patient’s residence, a single-family home built in the early 1910s that appeared to be in good condition and was served by a municipal water supply system. Both cultures were positive for L. pneumophila. Starting on day 52 and following advice in a 2010 home guidance manual (2), a plumber drained, cleaned with chlorine, and superheated to 148°F (64.4°C) the home’s water heater and then flushed the fixtures over a 3-day period. The showerheads were also soaked in vinegar to remove hard water scale. As part of the case investigation and to determine whether remediation was successful, DPH epidemiologists collected samples in the home on day 62. Eight fixtures were sampled: the two showers, one handheld shower wand, a bathroom sink faucet, two kitchen sink sprayers, the water heater tank, and the whole-house humidifier. Samples were cultured for Legionella at WSLH. Cultures from the bathroom faucet and the kitchen sprayers were positive for L. pneumophila, indicating that the bacteria remained in the home’s water system. The home guidance manual (2) was shared with the other resident of the home, who was not immunocompromised and did not become ill. Practices to prevent Legionella growth within the water system were discussed, such as adhering to recommended water heater settings and maintenance schedules and flushing fixtures after lack of use (e.g., after returning from vacation). The other resident also was encouraged to seek medical advice if they developed symptoms of respiratory illness.

On day 75, WSLH reported that the isolates from the home environmental samples collected on day 62 and the patient’s clinical isolate matched by pulsed-field gel electrophoresis patterns. The isolates were sent to CDC for whole-genome multilocus sequence typing and on day 114 were identified as L. pneumophila serogroup 3, sequence type 93, with 99.7% shared allele content among strains. The patient’s home was determined to be the most likely source of infection.

Discussion

In Wisconsin, the number of reported confirmed Legionnaires’ disease cases has increased more than 400% from 63 in 2010 to 330 in 2018; this increase is consistent with a national 4.5-fold increase in the incidence rate from 2000 to 2015 (1). Approximately 9% of Legionnaires’ disease cases in the United States are fatal (3), and two thirds of patients with confirmed cases during 2015 had not traveled or been in a health care or assisted living setting during their presumed exposure period (1).

This Wisconsin case highlights the potential for persons at risk for Legionnaires’ disease (e.g., patients with a weakened immune system) to be exposed to Legionella through home water systems containing the bacteria and also demonstrates the difficulty of remediation. Evidence of Legionella in residential potable water has been widely documented (4). Published guidance for prevention of Legionella growth and spread is limited to complex building water systems through water management programs and, when indicated, immediate control measures such as point-of-use filters (5,6). Evidence regarding the burden (i.e., morbidity and mortality) from home-associated Legionnaires’ disease and the usefulness and feasibility of testing and remediation in residential settings is limited. Increased efforts to understand the burden and risk associated with residential settings could inform prevention guidance.

This case also highlights the value of obtaining lower respiratory tract specimens for both patient treatment (identification of less common Legionella infections) and public health investigation (confirmation of infection source). Nonserogroup 1 L. pneumophila infections cannot be routinely detected using the Legionella urinary antigen test but can be detected by polymerase chain reaction or culture of lower respiratory tract secretions (e.g., sputum or BAL fluid). Importantly, sputum specimens can be successfully cultured for Legionella even if the specimen is considered low quality (7). Because timely antibiotic treatment can affect patient survival, CDC recommends concurrent ordering of Legionella urinary antigen test and a culture of lower respiratory tract secretions for patients with suspected Legionnaires’ disease (8).

Acknowledgments

Patient’s family members and local public health department; Wisconsin State Laboratory of Hygiene; Wisconsin Department of Health Services, Division of Public Health, Bureau of Communicable Diseases, Communicable Diseases Epidemiology Section; CDC’s Legionella team; Kris Bisgard, CDC.

Corresponding author: Anna Kocharian, [email protected], 608-267-9004.


1Epidemic Intelligence Service, CDC; 2Bureau of Communicable Diseases, Division of Public Health, Wisconsin Department of Health Services; 3Infection Control, UW Health, Madison, Wisconsin.

All authors have completed and submitted the International Committee of Medical Journal Editors form for disclosure of potential conflicts of interest. No potential conflicts of interest were disclosed.

References

  1. CDC. Legionnaires’ disease surveillance summary report, United States: 2014–2015. Atlanta, GA: US Department of Health and Human Services, CDC; 2018. https://www.cdc.gov/legionella/health-depts/surv-reporting/2014-15-surv-report-508.pdf
  2. Freije MR. Protect yourself from Legionnaires’ disease: the waterborne illness that continues to kill and harm. Solona Beach, CA: HC Information Resources; 2010.
  3. Dooling KL, Toews KA, Hicks LA, et al. Active bacterial core surveillance for legionellosis—United States, 2011–2013. MMWR Morb Mortal Wkly Rep 2015;64:1190–3. CrossRef PubMed
  4. Orkis LT, Harrison LH, Mertz KJ, Brooks MM, Bibby KJ, Stout JE. Environmental sources of community-acquired Legionnaires’ disease: a review. Int J Hyg Environ Health 2018;221:764–74. CrossRef PubMed
  5. CDC. Developing a water management program to reduce Legionella growth and spread in buildings. Atlanta, GA: US Department of Health and Human Services, CDC; 2017. https://www.cdc.gov/legionella/downloads/toolkit.pdf
  6. CDC. Things to consider: healthcare-associated cases and outbreaks. Atlanta, GA: US Department of Health and Human Services, CDC; 2017. https://www.cdc.gov/legionella/health-depts/healthcare-resources/cases-outbreaks.html
  7. Murdoch DR. Diagnosis of Legionella infection. Clin Infect Dis 2003;36:64–9. CrossRef PubMed
  8. CDC. Legionella (Legionnaires’ disease and Pontiac fever): diagnosis, treatment, and prevention. Atlanta, GA: US Department of Health and Human Services, CDC; 2018. https://www.cdc.gov/legionella/clinicians/diagnostic-testing.html
Return to your place in the textFIGURE. Timeline of events during investigation of a fatal case of Legionnaires’ disease — Wisconsin, 2018*
The figure shows a timeline of events in the 2018 investigation of a fatal case of Legionnaires’ disease in a resident of Wisconsin.

Abbreviations: BAL = bronchoalveolar lavage; PFGE = pulsed-field gel electrophoresis; wgMLST = whole-genome multilocus sequence typing; WSLH = Wisconsin State Laboratory of Hygiene.

*Approximate days before and recorded days after patient’s hospital admission (day 0).

TABLE. Environmental sampling and culture results from a health care facility and a personal residence during investigation of a fatal case of Legionnaires’ disease — Wisconsin, 2018Return to your place in the text
Sampling site Days after patient’s hospital admission Sample type* Aerator/ Showerhead removed Affiliation of laboratory Legionella pneumophila culture result CFU ml
Health care facility
Outpatient clinic
Exam room faucet 17 Bulk (550 ml), initial No Hospital Neg
Warm water pool 17 Bulk (550 ml) N/A Hospital Neg
Emergency department
Exam room faucet 17 Bulk (550 ml), initial No Hospital Neg
Ice machine 17 Bulk (550 ml) N/A Hospital Neg
Inpatient
Patient room sink faucet 17 Bulk (550 ml), initial No Hospital Neg
Bulk (550 ml), 2 min No Hospital Neg
40 Bulk (550 ml), warm No Hospital Neg
WSLH Neg
Swab Yes Hospital Neg
WSLH Neg
Patient room shower 17 Bulk (550 ml), initial No Hospital Neg
Bulk (550 ml), 2 min No Hospital Neg
40 Bulk (550 ml), warm No Hospital Neg
WSLH Neg
Swab Yes Hospital Neg
WSLH Neg
Kitchen sink 17 Bulk (550 ml), initial No Hospital Neg
Ice machine 17 Bulk (550 ml) N/A Hospital Neg
Intensive care unit
Patient room sink 17 Bulk (550 ml), initial No Hospital Neg
40 Bulk (550 ml), warm No Hospital Neg
WSLH Neg
Swab Yes Hospital Neg
WSLH Neg
Patient home samples
Bathroom 1
Shower 26 Bulk, 550 ml, warm No Hospital Pos 2.54
62 Bulk (250 ml), warm Yes WSLH Neg
Swab Yes WSLH Neg
Bathroom 2
Shower 26 Bulk, 550 ml, warm No Hospital Pos 0.36
62 Bulk (250 ml), warm Yes WSLH Neg
Swab Yes WSLH Neg
Shower wand 62 Bulk (250 ml), warm No WSLH Neg
Sink 62 Bulk (250 ml), warm No WSLH Pos 0.05
Kitchen
Sink #1 sprayer 62 Bulk (250 ml), warm No WSLH Pos 0.11
Sink #2 sprayer 62 Bulk (250 ml), warm No WSLH Pos 0.26
Entire home
Water heater 62 Bulk (250 ml) N/A WSLH Neg
Humidifier 62 Swab N/A WSLH Neg

Abbreviations: CFU = colony forming units; N/A = not applicable; Neg = no Legionella pneumophila isolated; Pos = Legionella isolated; WSLH = Wisconsin State Laboratory of Hygiene.
* Bulk samples were either drawn immediately when the faucet was turned on, after 2 minutes of hot water flow, or after running the water until warm.
Sinks have aerators, and showers have showerheads. Removal of the aerator or showerhead is required to obtain a swab sample. Procedural differences or inability to remove an aerator or showerhead for a fixture caused the variation.


Suggested citation for this article: Schumacher A, Kocharian A, Koch A, Marx J. Fatal Case of Legionnaires’ Disease After Home Exposure to Legionella pneumophila Serogroup 3 — Wisconsin, 2018. MMWR Morb Mortal Wkly Rep 2020;69:207–211. DOI: http://dx.doi.org/10.15585/mmwr.mm6908a2.

MMWR and Morbidity and Mortality Weekly Report are service marks of the U.S. Department of Health and Human Services.
Use of trade names and commercial sources is for identification only and does not imply endorsement by the U.S. Department of Health and Human Services.
References to non-CDC sites on the Internet are provided as a service to MMWR readers and do not constitute or imply endorsement of these organizations or their programs by CDC or the U.S. Department of Health and Human Services. CDC is not responsible for the content of pages found at these sites. URL addresses listed in MMWR were current as of the date of publication.

All HTML versions of MMWR articles are generated from final proofs through an automated process. This conversion might result in character translation or format errors in the HTML version. Users are referred to the electronic PDF version (https://www.cdc.gov/mmwr) and/or the original MMWR paper copy for printable versions of official text, figures, and tables.